7.3.3 Keypad control menu (M3)
In the
Keypad Controls Menu
, you can choose the control place, edit the frequency reference and change
the direction of the motor. Enter the submenu level with the
Menu button right
.
Code Parameter Min Max Unit Default Cust ID Note
P3.1 Control place 1 3 1
125
1=I/O terminal
2=Keypad
3=Fieldbus
R3.2 Keypad reference
Par.
2.1.1
Par. 2.1.2 Hz
P3.3 Direction (on keypad) 0 1 0
123
0=Forward
1=Reverse
R3.4 Stop button 0 1 1
114
0=Limited function of Stop
button
1=Stop button always
enabled
Table 7-2. Keypad control parameters, M3
7.3.3.1 Selection of control place
There are three different places (sources) which the frequency converter can be controlled from. For each
control place, a different symbol will appear on the alphanumeric display:
Control place Symbol
I/O terminals
Keypad (panel)
Fieldbus
Change the control place by entering the edit mode with the
Menu button right
. The options can then be
browsed through with the
Browser buttons
. Select the desired control place with the
Enter button
. See the
diagram on the next page.
Figure 7-6. Selection of control place
I/O term
Keypad
Bus/Comm
P1
P4
READY
I/Oterm
READY
I/Oterm
READY
I/Oterm
READY
I/Oterm
enter
READY
Keypad
STOP
STOP
STOP
STOPSTOP
Keypad control
Control Place
I/O Remote
Control Place
I/O Remote
Control Place
Keypad
Control Place
Keypad